CA2-KN22-M7 – SCHNEIDER TeSys K control relay – 2 NO + 2 NC – <= 690 V – 220…230 V AC coil — SCHNEIDER

Product image for reference. Check the manufacturer's documentation for exact appearance and dimensions.

SCHNEIDER

CA2-KN22-M7 – SCHNEIDER TeSys K control relay – 2 NO + 2 NC – <= 690 V – 220…230 V AC coil

Brand
SCHNEIDER
Model / part no.
CA2-KN22-M7
Category
Switches & Relays
Type
Control Relays & Sockets
Price and availability on request. Our team confirms both with every quotation.
Specifications
Product NameTeSys CAK
BrandSchneider Electric
SeriesTeSys
TypeControl Relay
Device Short NameCA2K
Contactor ApplicationControl Circuit
Utilisation CategoryAC-15, DC-13
Pole Contact Composition2 NO + 2 NC
Rated Operational Voltage ([Ue])≤ 690 V, ≤ 400 Hz
Control Circuit TypeAC at 50/60 Hz
Control Circuit Voltage ([Uc])220…230 V AC, 50/60 Hz
Rated Thermal Current ([Ith])10 A (at 50 °C)
Rated Making Capacity (Irms)110 A (IEC 60947)
Associated Fuse Rating
  • 10 A gG (IEC 60947)
  • 10 A gG (VDE 0660)
Rated Insulation Voltage ([Ui])
  • 690 V (IEC 60947)
  • 750 V (VDE 0110 group C)
  • 690 V (BS 5424)
  • 600 V (CSA C22.2 No 14)
Mounting SupportRail, Plate
Connections – Terminals
  • 1× solid 1.5–4 mm²
  • 2× solid 1.5–4 mm²
  • 1× flexible 0.75–4 mm² with cable end
  • 2× flexible 0.75–4 mm² without cable end
  • 1× flexible 0.34–1.5 mm² with cable end
  • 2× flexible 0.34–1.5 mm² without cable end
Tightening Torque1.3 N·m (flat Ø 6 mm / Philips No 2 / Pozidriv No 2)
Drop-out0.2…0.75 Uc (at <50 °C)
Operational0.8…1.15 Uc (at <50 °C)
Operating Time
  • 10–20 ms coil de-energisation and NO opening
  • 10–20 ms coil energisation and NO closing
  • 15–25 ms coil de-energisation and NC closing
  • 5–15 ms coil energisation and NC opening
Mechanical Durability10 million cycles
Maximum Operating Rate10,000 cycles/hour
Immunity to Microbreaks2 ms
Inrush Power30 VA (at 20 °C)
Hold-in Power Consumption4.5 VA (at 20 °C)
Heat Dissipation1.3 W
Minimum Switching Voltage17 V
Minimum Switching Current5 mA
Non-Overlap Distance0.5 mm
Insulation Resistance> 10 MΩ
Dimensions (HxWxD)58 x 45 x 57 mm
Net Weight0.18 kg
Standards
  • EN/IEC 60947-4-1
  • GB/T 14048.4
  • UL 60947-4-1
  • CSA C22.2 No 60947-4-1
  • JIS C8201-4-1
CertificationsCB Scheme, CCC, UL, CSA, EAC, CE, UKCA
IP Degree of ProtectionIP2X
Protective TreatmentTC (IEC 60068)
Operating Temperature-25 to +50 °C
Storage Temperature-50 to +80 °C
Operating Altitude2000 m (without derating)
Flame Retardance
  • V1 (UL 94)
  • Requirement 2 (NF F 16-101, NF F 16-102)
Vibrations (open)2 Gn, 5–300 Hz (IEC 60068-2-6)
Vibrations (closed)4 Gn, 5–300 Hz (IEC 60068-2-6)
Shocks (open)10 Gn, 11 ms (IEC 60068-2-27)
Shocks (closed)15 Gn, 11 ms (IEC 60068-2-27)

Questions about this product? Call +974 4469 1757 or email info@umeelec.com.